Delphys GP 2.0 160-800 kVA/kW

Võimsustele 160 kuni 800 kVA/kW
Kõrge kasuteguriga kompromissitu UPSi lahendus

The solution for

  • Data centres
  • Telecommunications
  • Service sector
  • IT Networks/ Infrastructures

Advantages
Energy Saving: high efficiency without compromise

  • Offers the highest efficiency in the market using VFI – Double Conversion Mode, the only UPS working-mode that assures total load protection against all mains quality problems.
  • Ultra high efficiency output independently tested and verified by an international certification organization in a wide range of load and voltage operating condition.
  • Ultra high efficiency in VFI mode is provided by an innovative topology (3-Level technology) that has been developed for all the Green Power UPS ranges.

Full-rated power: kW=kVA

  • No power downgrading when supplying the latest generation of servers (leading or unity power factor).
  • Real full power, according to IEC 62040: kW=kVA (unity power factor design) means 25% more active power available compared to legacy UPS.
  • Suitable also for leading power factor loads down to 0.9 without apparent derating.

Significant cost savings (TCO)

  • Maximum energy saving thanks to 96% efficiency in true double conversion mode: 50% saving on energy losses compared to legacy UPS gives significant savings in energy bill.
  • Up to 99% efficiency with FAST ECOMODE
  • UPS “self-paying” with energy saving.
  • Energy Saver mode for global efficiency improvement on parallel systems.
  • kW=kVA means maximum power available with the same UPS rating: no overdesign cost and therefore less €/kW.
  • Upstream infrastructure cost optimization (sources and distribution), thanks to high performance IGBT rectifier.

Extended battery life and performance:

  • Long life battery,
  • Very wide input voltage and frequency without battery use,
  • EBS (Expert Battery System) charging management improves battery service life
  • BHC INTERACTIVE: Accurate battery monitoring with UPS interactivity for even more prolonged service life

    Technical data
     

    Sn (kVA) 160 200 250 320 400 500 600 800
    Pn [kW] 160 200 250 320 400 500 600 800
    Input / output 3/3
    Parallel configuration up to 4 MW
    Input
    Rated voltage 400V 3ph
    Voltage tolerances 200 V to 480 V (1)
    Rated frequency 50 / 60 Hz
    Frequency tolerance ± 10 Hz
    Power factor/THDI > 0.99 / < 2.5%(2)
    Output
    Rated voltage 3ph + N 400 V
    Voltage tolerance static load  static load ±1% dynamic load in accordance with VFI-SS-111
    Rated frequency 50 / 60 Hz
    Frequency tolerance ± 2% (configurable for GenSet compatibility)
    Total output voltage distortion - linear load ThdU < 1.5%
    Total output voltage distortion - non-linear load (lEC 62043-3) ThdU < 3%
    Short circuit current up to 3.4 x In
    Bypass
    Rated voltage rated output voltage
    Voltage tolerance ± 15% (configurable with from 10% to 20%)
    Rated frequency 50/60 Hz
    Frequency tolerance ± 2% (configurable for GenSet compatibility)
    Efficiency
    Online mode @ 40 % of load up to 96%
    Online mode @ 75 % of load up to 96%
    Online mode @ 100 % of load up to 96%
    Fast EcoMode up to 99%
    Environment
    Operating ambient temperature from 10 °C up to +40 °C (1) (from 15 °C to 25 °C for maximum battery life)
    Relative humidity 0% - 95% without condensation
    Maximum altitude 1000 m without derating (max. 3000 m)
    Acoustic level at 1 m (ISO 3746) <65 dBA <67 dBA <70 dBA <68 dBA <70 dBA <72 dBA <74 dBA
    UPS Cabinet
    Dimensions (W x D x H) 700 x 800 x 1930 mm 1000x 950x 1930 mm 1400 x 800 x 1930 mm 1600x 950x 1930 mm 2800 x 950 x 2055 mm 3700 x 950 x 2060 mm
    Weight 470 kg 490 kg 850 kg 980 kg 1000 kg 1500 kg 2300 kg 3400 kg
    Degree of protection IP 20 (other IP as option)
    Colours cabinet: RAL 7012, door: silver grey
    Standards
    Safety IEC/EN 62040-1, EN 60950-1, AS 62040.1.1, AS 62040.1.2
    EMC IEC/EN 62040-2, AS 62040.2
    Performance VFI-SS-111 - IEC/EN 62040-3, AS 62040.3
    Product declaration CE, RCM (E2376)

    (1) Worst condition (Auxiliary Mains not available)